top of page


ODES WT-32 Synchro-Check: Safe Switching Between Dead-Bus and Synchronism Check
Dead-Bus vs Synchronism Check Is Not a “Preference” – It’s a Different Close Logic In manual synchronizing / automatic synchro-check systems, “dead-bus check” is not just another panel habit. It changes the criterion for closing the breaker : Synchronism check (synchro-check) – close is permitted only when voltage, frequency and phase angle are within defined limits. Dead-bus / dead-line check – close is permitted only when the bus/line is confirmed de-energized (or very

TonyZhang
Jan 184 min read


Choosing High-Power, EMC-Hardened Time Relays for HV Control – Meet ODES STR-F1
Why HV Primary Control Now Demands “High-Power, EMC-Hardened” Time Relays In high-voltage circuit breaker control circuits, timing is not just a detail – it is part of the protection and interlocking function itself. But the environment around primary equipment is harsh: Strong electromagnetic disturbance from switching operations Inrush and back-EMF from trip/close coils and contactors Induced voltages on long control cables Several utilities now explicitly require that ti

TonyZhang
Jan 155 min read


Mastering HV Breaker Timing: ODES STR-F2 for Three-Phase Disagreement and Spring-Charging
Two “Small” Circuits That Decide HV Breaker Behaviour In high-voltage circuit breaker control, two secondary circuits quietly determine whether the primary equipment behaves as designed: Three-phase disagreement supervision Spring-charging (energy-storage) motor control If their timing is unstable, the result can be: Spurious three-phase disagreement alarms or trips caused by transient contact bounce Spring-charging motors running too long or starting simultaneously, stres

TonyZhang
Jan 154 min read
bottom of page
