Instrumentation Engineer’s 3-Minute PT100 Check: Fix “No Output” on STT Without Replacing the Transmitter
1. “STT Has No Output?” – Often the Symptom, Not the Root Cause On a recent project, an STT temperature transmitter had already been wired into the PLC analogue input. During pre-commissioning, that channel showed: Temperature value fixed or not updating in the HMI 4–20 mA signal not within the expected range The first reaction on site was predictable: “The transmitter has no output. Is it faulty?” Instead of immediately replacing the device, we started at the input . In ma

TonyZhang
Feb 134 min read


“See the Heat Before It Hurts” — How the TSW Series Makes Transformer Temperature Visible, Smart, and Safer
In most substations, temperature data for transformers still hides behind the control room screens. Oil, core, and winding temperatures — the “three thermometers” that reveal a transformer’s true condition — are often invisible at the equipment itself. Operators walk back and forth between panels and SCADA terminals just to confirm if things are running hot or cold. In regions like Inner Mongolia, Gansu, and Xinjiang , where on-site staffing is essential, maintenance teams

TonyZhang
Nov 23, 20253 min read


Temperature Signal Conversion in Transformer Monitoring Systems
The Role of Temperature Transmitters in Protection and Monitoring In modern protection and control systems, accurate temperature measurement is essential to assess transformer health and prevent thermal faults. Parameters such as core temperature , winding temperature , and oil temperature form the foundation of transformer “tri-temperature” monitoring. The STT Series temperature transmitters from ODES are engineered for this purpose. Designed to meet IEEE and

TonyZhang
Oct 22, 20253 min read


Reliable Heating Cable Control in Extreme Cold: ODES Smart Temperature Controller
Problem Statement Gas-insulated switchgear (GIS) and other gas-insulated systems depend on stable gas pressure and temperature to...

TonyZhang
Aug 31, 20252 min read